INW Series grid-interactive hybrid inverter, 3.3–10.5 kW
The INV's grid-interactive sibling: IP54, feed-in to the grid, generator input, and the same 3.3–10.5 kW range for sites that sell power back.
Product image
- Brand
- HighIdea
- Type
- Single-phase grid-interactive hybrid inverter, IP54
- Typical applications
- Grid-tied residential solar with backup, small commercial self-consumption, generator-hybrid sites
- Models in range
- IN 3600-24, INW 6500-48, INW 12000-48
- Category
- Solar Inverters
Export changes the design
Once an inverter can export, the utility's requirements arrive with it: a grid code, an anti-islanding test, a power factor setting, and often a limit on export current. The INW carries those settings in firmware, selected at commissioning from a country list.
Mechanically, the INW is the outdoor-rated version of the INV platform — IP54 instead of an open chassis, with a sealed cable entry and a UV-stable cover. That lets it mount on an outside wall next to the array rather than in a plant room.
Generator hybrid
On sites with a diesel generator, the INW uses the generator as a charge source rather than a permanent supply: the generator runs at its efficient point to charge the battery, then stops, and the inverter supplies the load from the battery. That cycle typically cuts fuel use by 30–50 % against continuous generator running, and it cuts engine hours, which is the larger maintenance cost.
Parallel and phase balance
Up to nine units parallel on one phase. On a single-phase supply that is usually done for capacity, but it is also done for resilience: three units in parallel, one fails, the site keeps running at reduced capacity.
Key Features
- 3.3 kW to 10.5 kW, 24 V and 48 V battery
- Grid feed-in as well as self-consumption
- IP54 enclosure for semi-outdoor installation
- Built-in 100 A MPPT solar charger, 40–450 V window
- Generator input, with programmable charge current
- Parallel up to 9 units
- Dual AC output and LCD display
- Wi-Fi monitoring, lithium battery activation
Applications
Residential self-consumption with export
Runs the house from PV first, charges the battery, then exports the surplus under the local feed-in tariff.
Generator-hybrid sites
Accepts a diesel generator on the AC input, reducing generator hours by cycling the battery instead.
Small commercial
Three units in parallel cover a shop or workshop with three-phase-ish loads on single-phase supply.
FAQ
What is the difference from the INV series?
Can it export without a battery?
Does it work with a generator?
How is the grid code set?
Specification reference
| Parameter | IN 3600-24 | INW 6500-48 | INW 12000-48 |
|---|---|---|---|
| PV Input | |||
| Max. Input Power (kW) | 5 | 9 | 1MPPT:9KW; 2MPPT:7.5KW+7.5KW |
| Max. Input Current (A) | 18 | 27 | 1MPPT:27A; 2MPPT:22.5A+22.5A |
| PV Input Short-circuit Current (A) | 22 | 33 | 33 |
| Open Circuit Voltage (VDC) | 500 | ||
| Start-up Voltage (VDC) | 60 | 80 | 80 |
| MPPT Voltage (VDC) | 40~450 | 60~450 | 60~450 |
| AC Input | |||
| Rated Input Voltage (VAC) | 208 / 220 / 230 / 240; L+N+PE | ||
| Voltage Range (VAC) | 90-280±3V(Normal) / 170-280±3V(UPS) | ||
| Frequency (Hz) | 50 / 60 | ||
| Max. Bypass Input Current (A) | 20 | 40 | 70 |
| Parallel Quantity | NA | 9 Max. 9-unit parallel operation | 6 Max. 6-unit parallel operation |
| AC Output | |||
| Rated Capacity (kW) | 3.6 | 6.5 | 12 |
| Output Power (battery mode) (kW) | 3.3 | 6.5 | 10.5 |
| Voltage (VAC) | 208 / 220 / 230 / 240 | ||
| Frequency (Hz) | 50/60Hz±0.1% | ||
| Output Wave Form | Pure Sine Wave | ||
| Battery Mode Overload Capacity | 60s @ 102%-120% Load; 10s @ 120%-200% Load | ||
| Battery Mode Max. Efficiency | 92.7%@24VDC | 93%@48VDC | 94%@48VDC |
| Switch Time (ms) | <10 | ||
| Battery | |||
| Nominal Voltage(VDC) | 24 | 48 | 48 |
| Max. AC Charge Current (A) | 100 | 120 | 160 |
| Max. PV Charge Current (A) | 100 | 120 | 160 |
| Max. Charge Current (PV + AC) (A) | 100 | 120 | 160 |
| Max.Discharge Current (A) | 160 | 160 | 220 |
| Operating Voltage Range (VDC) | 21.6Vdc~29.2Vdc | 43.2Vdc~58.4Vdc | 43.2Vdc~58.4Vdc |
| General Data | |||
| Reveal | LCD | ||
| Communication | RS485 /CAN / USB | ||
| Monitoring | WIFI/4G (Optional) | ||
| Ingress Protection | IP54 | ||
| Operating Temperature | -10 °C~55 °C | ||
| Relative Humidity | 5% ~ 95% (Non-condensing) | ||
| Max. Operating Altitude | 4000m (Derating above 2000m) | ||
| DIMENSION | |||
| NW (Kg) | 6.1 | 8.3 | 14.2 |
| GW (Kg) | 7.2 | 9.5 | 15.7 |
| Products Size(W*H*D)mm | L420xW289xH100 | L410xW331xH135 | L495xW425xH132 |
| Package Size(W*H*D)mm | L500xW369xH170 | L472xW405xH210 | L551xW491xH191 |
| Quantity 20GP | 560 | 440 | 360 |
| Quantity 40GP | 1240 | 960 | 750 |
| Quantity 40HQ | 1612 | 1320 | 1000 |
Specifications subject to the latest factory data. Final configuration is sized against the actual load, backup runtime and site power conditions — this table is for pre-selection only.