FAQ: Telecom Base Station Inverter Selection

Last updated 2026-08-25

Telecom base stations run on -48VDC power — the global standard. While network gear uses DC directly, AC-powered equipment (air conditioners, microwave backhaul, tower-mounted amplifiers, maintenance tools) needs a dedicated telecom Inverter. High Idea Power E Series and H Series provide purpose-built 48VDC-to-220VAC conversion with telecom-grade reliability.

Model Power DC Input Form Factor Battery
E1K-36 1000VA/800W 36V (10AH built-in) 1U rack Built-in LiFePO4
E1KS-48 1000VA/800W 48V (40–60VDC) 2U rack External LD48
E2KS-48 2000VA/1600W 48V (40–60VDC) 2U rack External LD48
E3KS-48 3000VA/2400W 48V (40–60VDC) 2U rack External LD48
H1K-48 1000VA/800W 36–60VDC 2U rack External
H3K-48 3000VA/2400W 36–60VDC 2U rack External

All E Series: online double-conversion, zero transfer (AC-DC: 0ms, Inverter-Bypass: <4ms), output THD <3%, RS232 + intelligent slot. E1K-36 includes integrated 36V10AH Lithium Battery UPS module.

1. LD48 Series battery packs?

Model Capacity Dimensions (mm) Weight
LD4810 48V 10AH 432×88×310 10kg
LD4820 48V 20AH 432×88×310 16kg
LD4830 48V 30AH 432×88×440 22kg
LD4830PRO 48V 30AH 432×88×600 24kg
LD4850 48V 50AH 432×88×440 28kg
LD4850PRO 48V 50AH 432×88×600 30kg

Built-in BMS: deep discharge cutoff at 40VDC, overcharge limit 57VDC, cell balancing, short-circuit & reverse polarity protection, temperature-compensated charging. Multiple packs parallel for extended runtime. E3KS-48 + LD4850 ≈ 30 min at 2000W.

2. Deployment scenarios?

Macro base stations: H3K-48 + LD4850PRO, outdoor cabinet. Micro cells: E1K-36 self-contained 1U, 9kg, single-person install. Indoor DAS: E1KS-48/E2KS-48 + LD4820, front-access maintenance. Tower sharing: HM Series N+1 parallel (HM3K–HM15K, 48VDC) multi-tenant from shared battery plant.

3. Environmental ratings for outdoor cabinets?

E Series: -10°C to +40°C. H Series: -10°C to +40°C. RT-4860 rectifier: -40°C to +65°C. HM Series: -33°C to +40°C (Arctic/high-altitude). LD48 LiFePO4 tolerates wider temperatures than VRLA. Humidity 10–90% (HM), 20–90% (E).

4. Hybrid energy integration (solar + grid + battery)?

Solar MPPT → 48VDC bus. RT-4860 rectifier (54Vdc, 90–280VAC input, ≥91% efficient, ripple ≤2mV) supplements from grid. LD48 battery stores excess solar. E/H Inverter converts 48VDC to 220VAC. Programmable priority: solar → battery → grid → generator, minimizing diesel consumption at off-grid sites.

5. Remote monitoring?

SNMP card (Ethernet, v1/v2c/v3), MODBUS RTU (RS485 to RTU), dry contacts (AC Fail, Battery Low, Fault, Overload), CloudUPS platform (web dashboard, SMS/email alarms, multi-site fleet management). NOC monitors hundreds of sites from a single console.

Email Us WhatsApp