FAQ: Rack-Mount UPS Selection Guide

Last updated 2026-08-25

Rack-mount UPS systems are essential for data centers, server rooms, and telecom cabinets where space efficiency and front-access maintenance are critical. This guide covers High Idea Power’s E Series and ET Series rack-mount UPS with real specifications to help you choose the right model.

1. What rack-mount UPS options does High Idea Power offer?

E Series — Online Rack-Mount UPS (1–3KVA):

Model Capacity DC Voltage Battery Dimensions (mm)
E1K-36 1000VA/800W 36V Built-in 36V 10AH LiFePO4 432×88×300
E1KS-48 1000VA/800W 48V External ≥10AH LiFePO4 432×88×300
E2KS-48 2000VA/1600W 48V External ≥20AH LiFePO4 432×88×440
E3KS-48 3000VA/2400W 48V External ≥30AH LiFePO4 432×88×440

ET Series — Online Rack/Tower UPS (1–10KVA): ET1K through ET10KRS, with select models featuring built-in LiFePO4 batteries. The ET3K (3000VA/2400W) with built-in 48V 30AH battery provides 25 min at 2000W and 90 min at 250W.

2. What does “online double-conversion” mean for rack-mount servers?

Online double-conversion means the Inverter continuously powers connected equipment — AC mains is rectified to DC, then inverted back to pure AC. This eliminates any transfer time (0ms switchover), providing pure sine wave output at 220VAC ±3% regardless of input quality. For data centers, this prevents micro-outages that crash RAID controllers and corrupt databases.

3. ET1K vs. ET3K — which for a small server room?

  • ET1K (1000VA/800W): 1–2 entry-level servers, network switch, small NAS. Built-in 36V 15AH LiFePO4 delivers ~35 minutes at 600W.
  • ET3K (3000VA/2400W): 2–3 rack servers, multiple PoE switches, surveillance NVR. Built-in 48V 30AH LiFePO4 provides 25 min at 2000W, 40 min at 1700W, 70 min at 750W.

4. E Series vs. ET Series — key differences?

Feature E Series ET Series
Primary design Telecom base station, 19-inch rack General-purpose server room
1U compatible Yes (E1KS-48-1U) No (minimum 2U)
Interfaces RS232 + dry contact RS232 + intelligent slot (SNMP expandable)
Target Telecom, railway, utility IT server rooms, enterprise

5. What battery configuration for extended runtime on ET6KRS/ET10KRS?

Both require a 192V DC battery bank — typically four LD4830 or LD4850 48V Lithium Battery packs in series. An ET10KRS at 50% load (4KW) with four LD4850 packs provides ~15–20 minutes. Doubling to eight packs extends to 35–45 minutes. Battery expansion is modular — add strings as needed.

6. Can rack-mount UPS units go beyond server rooms?

Yes. Operating range is -10°C to 40°C, humidity 20%–90%. The E series specifically targets railway signaling, utility substations, telecom base stations, and public security infrastructure — environments where front-access maintenance is mandatory.

7. What remote monitoring accessories are available?

  • RS232 serial port: Standard for local management on all models.
  • Intelligent expansion slot (ET series): Accepts SNMP cards, AS400 relay cards, and Smart UPS cloud monitoring cards for web-based remote management.
  • Dry contact interface (E series): Built-in for BMS and SCADA integration.