RT4860 1U Embedded Telecom Rectifier System

A complete 48V telecom power plant in 1U: two rectifier modules, one controller and integrated battery / load distribution.

RT4860 (RT48120 family) Product image
Appearance may vary by configuration; final specifications per quotation.
Brand
HighIdea
Type
Embedded 48VDC telecom rectifier system (1U 19-inch)
Typical applications
Small PBX, access networks, transmission equipment, mobile and satellite communication, microwave stations
Models in range
RT4860 standard (2 x 4830 modules), RT48120 higher-capacity configuration
Category
Switching Power Supplies & Rectifiers

The RT4860 is a complete 48V embedded telecom power system in a 1U 19-inch frame. It is built for small program-controlled exchanges, access networks, transmission equipment, mobile communication, satellite earth stations and microwave links, and for any other site that needs a compact, monitored DC plant.

Design notes

The standard system contains two 4830 rectifier modules, one monitoring module and DC distribution with a battery circuit and a load circuit. While mains is healthy, the controller manages rectifier and distribution parameters according to preset values or operator commands. On mains failure the battery takes over; as the bus falls, the controller raises a low-voltage alarm at 46VDC and disconnects the load at 43VDC by default. Both thresholds and other monitoring data can be reconfigured from the host software. Output resumes automatically when mains returns. Above 55 deg C ambient the system derates its output to protect the modules.

Configuration

Confirm the load current, battery string capacity and chemistry, the number of distribution circuits, the alarm and disconnect setpoints, and the remote monitoring protocol. For a 24V bus see the RT2430 1U; for systems that must scale to 800A see the RT 30-800A.

Key Features

  • 1U 19-inch embedded frame for simple cabinet installation and front access
  • Two 4830 rectifier modules with automatic current sharing
  • Monitoring module controls rectifier and distribution parameters
  • Separate battery and load DC distribution as standard
  • Configurable low-voltage battery alarm and load disconnect thresholds
  • Automatic recovery when mains returns
  • Designed for unattended telecom and transmission sites

Applications

Access & transmission rooms

Compact 48VDC plant for access network and optical transmission equipment.

Microwave & satellite sites

Unattended sites where automatic recovery and battery protection matter.

Small exchanges

1U power plant with separate battery and load distribution.

FAQ

What is included in the standard system?
Two 4830 rectifier modules, one monitoring module, and DC distribution with one battery circuit and one load circuit. Extra breakers and monitoring options are available.
What happens when mains fails?
The battery string supplies the load. As the voltage falls, the controller raises a low-voltage alarm at 46VDC and disconnects the load at 43VDC by default; both setpoints can be changed from the host software. Output restores automatically when mains returns.
Does it need a temperature-controlled room?
The system delivers full output in normal equipment-room conditions and derates output when ambient temperature reaches 55 deg C or more.

Related Models

Specification reference

DC output voltage42 - 58 VDC (48V nominal)
Mounting1U 19-inch rack
Standard configuration2 x 4830 rectifier modules + 1 monitoring module
DC distribution1 battery circuit + 1 load circuit
Battery low alarm46 VDC default, configurable
Load disconnect43 VDC default, configurable
Thermal behaviourOutput derated above 55 deg C ambient
MonitoringLocal controller with configurable setpoints; remote protocol options
Typical applicationsPBX, access network, transmission, microwave, satellite earth stations

Specifications subject to the latest factory data. Final configuration is sized against the actual load, backup runtime and site power conditions — this table is for pre-selection only.